Explosive atmospheres ATEX fans
Suitable for use in battery-charging rooms, fume cupboards and similar environments
Compact design
Speed controllable with transformer
Mounting bracket as standard
Ex certification classification Ex de IIC T4 Gb
EX fans can be installed in any position, and their compact design makes them easy to install.
These fans are powered by specially manufactured EX motors and have impellers with forward-curved blades. The fan casing is cast in silumin and the impeller is manufactured from aluminium.
Datos nominales
Tensión (nominal)
400V
Frecuencia
50Hz
Fase(s)
3~
Potencia de entrada
796W
Corriente de entrada
1,89A
Revoluciones por minuto
2.777r.p.m.
Caudal de airemáximo
1.231m³/h
Temperatura del aire transportado
máximo 50°C
Temperatura maxima del aire transportado, con velocidad controladoa
50°C
Datos de ruido
Nivel de presion sonora a 3m (20m2 Sabin)
63dB(A)
Proteccion/Clasificacion
Grado de proteccion ,motor
IP65
Clase de aislamiento
F
Marca a prueba de explosiones
Ex de IIC T4 Gb
Certificado
Presafe 16ATEX8598X
Controlador y sensores
Temperatur ambiente y del conducto
-20 Para 50°C
Dimensiones y pesos
Peso
10kg
Otros
Tipo de motor
AC
Datos hidráulicos
Caudal de aire requerido
615 m³/h
Presión estática requerida
629 Pa
Caudal de aire de trabajo
615 m³/h
Presión en punto de trabajo
629 Pa
Densidad del aire
1.204 kg/m³
Potencia
429.5 W
Control - RPM del ventilador
2907 rpm
Intensidad
1.64 A
SFP
2.513 kW/m³/s
Control de tensión
400.0 V
Tensión de alimentación
400 V